Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM03741
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/18/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET T1.1; REQUIRED PLUMBING FIXTURES: IT IS LISTED AS TWO WATER CLOSETS PROVIDED, BUT ONLY ONE IS INDICATED ON SHEET A1.1. CLARIFY. 2. SHEET T1.1; REQUIRED PLUMBING FIXTURES: PER THE IBC SECTION 2902.2(2), FOR OCCUPANT LOADS OVER 15, SEPARATE FACILITIES ARE REQUIRED. THEREFORE, TWO WATER CLOSETS ARE REQUIRED, ONE FOR MALE, ONE FOR FEMALE. 3. SHEET A2.1; RCP KEYNOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. VERIFY. 4. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS. |
| 06/18/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/18/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/24/2014 | FRODRIG2 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/24/2014 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/24/2014 | FRODRIG2 | WATER | REVIEW | Needs Review | |
| 06/24/2014 | FRODRIG2 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 06/24/2014 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 06/24/2014 | FRODRIG2 | ENGINEERING | REVIEW | Needs Review |