Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM03739
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/18/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Per 2012 IBC & IFC, 4 exits are required. Doors immediately adjacent to each other do not qualify as separate exits. Refer to sections 1015 and 1021, and the commentary associated with these sections. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/19/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |