Permit Number: T14CM03707
Parcel: 123153050

Address:
1225 E LEE ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM03707
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 7-21-14
Activity: T14CM03707
Address: 1225 E Lee St
Applicant: Tom Stevens

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

FOUNDATION PLAN:
1. Provide a complete foundation plan that includes a continuous footing minimum 12" below grade for all exterior walls, R403.1 & R403.1.6.

STRUCTURAL / FRAMING PLAN:
2. Provide a complete framing plan that indicates size, spacing and span of roof framing members, the location of braced wall panels and the sizes of all headers over wall openings, R403.1.6, Table 502.5(1), R602.10.2.2, R801.2.

ELEVATIONS:
3. Provide elevation drawings for new areas.

SECTIONS - DETAILS:
4. Provide a complete cross section drawing for new floor areas.

PLUMBING PLAN:
5. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, G2413.1, Table G2413.4 (1).

MECHANICAL PLAN:
6. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2014 CPIERCE1 REJECT SHELF Completed