Permit Number: T14CM03633
Parcel: 13337017F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03633
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.
2. The specified tankless water heater cannot limit the temperature of the hot water to 110 degrees Fahrenheit. Coordinate the temperature requirement note with the specified equipment. Reference: Section 303.2, IPC 2012.
06/13/2014 ROBERT SHERRY WATER REVIEW Approved
06/13/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/25/2014 AROMERO4 FIRE REVIEW Needs Review
08/25/2014 AROMERO4 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/25/2014 AROMERO4 WWM REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2014 AROMERO4 APPROVAL SHELF Completed
08/25/2014 AROMERO4 OUT TO CUSTOMER Completed
08/25/2014 AROMERO4 REJECT SHELF Completed