Permit Number: T14CM03626
Parcel: 125111560

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03626
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2014 STEVE SHIELDS ZONING REVIEW Approved
06/13/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide thermal load and HVAC equipment-sizing calculations to confirm the specified heat pumps for each apartment type. Reference: Section R403.6, IECC 2012.
2. Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the new windows on the architectural drawings. Reference: Section R303.1.3, IECC 2012.
06/13/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
06/13/2014 ROBERT SHERRY WATER REVIEW Completed
06/13/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/13/2014 LOREN MAKUS ENGINEERING REVIEW Approved
06/13/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.
2. If the shower does not have a pre-fabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 417.5.2, IPC 2012.
3. Provide shower and tub/shower control valves that comply with the requirements of Sections 424.3 and 424.5, IPC 2012.
06/13/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/16/2014 LHANLY1 WWM REVIEW Passed
06/16/2014 KEN BROUILLETTE FIRE REVIEW Approved