Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2.0; ELEVATION KEYNOTES: NOTES 6 AND 7 WERE NOT LOCATED ON THE ELEVATIONS. VERIFY.
2. SHEET A3.0; SECTION KEYNOTES: NOTES 13 AND 14 WERE NOT LOCATED ON THE SECTIONS. VERIFY.
3. SHEET A3.0; SECTION KEYNOTES: FINISH THE DETAIL NUMBER IN NOTE 16.
4. SHEET A3.0; SECTION 6: NOTE 22 REFERENCES A 2"X2"X3/16" STEEL ANGLE. PROVIDE A NOTE FOR THE CONNECTION OF THE ANGLE TO THE MASONRY.
5. SHEET A4.0; SECTION 10: PROVIDE A NOTE FOR THE CONNECTION OF THE 2"X2"X3/16" ANGLE TO THE METAL STUDS.
6. SHEET S1.1; ROOF FRAMING PLAN: REVISE THE NORTH ARROW DIRECTION.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/12/2014 LOREN MAKUS ENGINEERING REVIEW Approved
06/12/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/13/2014 SPOWELL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
06/13/2014 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/13/2014 SPOWELL1 WATER REVIEW Needs Review
06/13/2014 SPOWELL1 ZONING REVIEW Needs Review
06/13/2014 SPOWELL1 WWM REVIEW Needs Review
06/13/2014 SPOWELL1 PLUMBING-COMMERCIAL REVIEW Needs Review
06/13/2014 SPOWELL1 FIRE REVIEW Needs Review