Permit Number: T14CM03587
Parcel: 11810006D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03587
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
06/12/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/12/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
06/12/2014 ROBERT SHERRY WATER REVIEW Completed
06/12/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET D1.0; DEMOLITION KEYNOTES: SEVERAL NOTES WERE NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET A2.0; KEYNOTES: SEVERAL KEYNOTES WERE NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A3.0; REFLECTED CEILING PLAN KEYNOTES: SEVERAL KEYNOTES WERE NOT LOCATED ON THE PLAN. VERIFY.
4. SHEET A4.0; KEYNOTES: VERIFY ALL KEYNOTES LISTED ARE ON THE ELEVATIONS.
5. SHEET A4.1; ELEVATIONS A AND B: THE TOP OF THE COUNTER MUST BE 2'-10" ABOVE THE FINISHED FLOOR FOR ACCESSIBILITY. REVISE.
6. SHEET A4.2; TELLER COUNTER: PROVIDE AN ACCESSILE PORTION OF THE COUNTER PER THE IBC SECTION 1109.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/12/2014 LHANLY1 WWM REVIEW Passed
06/12/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/12/2014 LOREN MAKUS ENGINEERING REVIEW Approved
06/12/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/13/2014 MARTIN BROWN FIRE REVIEW Approved