Permit Number: T14CM03575
Parcel: 114600820

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM03575
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2014 MARTIN BROWN FIRE REVIEW Approved
06/30/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
06/30/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved SHEET L2
1. The PV Racking Detail and the panel section shows anchoring into the top of a TJI L65 top cord with 2~5/16" x 3.5" lag screws. The top cord of this TJI is 1.5" deep and 2.5" wide with a 7/16" thick web member inserted more than halfway into the middle of the cord.
a. The lag screws are shown strattleing the top cord at a width which appears to be more then the top cord width of 2.5". Perhaps the bracket and bolt pattern should be parallel with the top cord?
b. Please provide a structural detail from Caiman Engineering (signed and sealed) showing the exact configuration of the anchoring system he is proposing. In addition please provide a letter of approval of this detail from the truss manufacturer.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2014 CPIERCE1 OUT TO CUSTOMER Passed