Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM03541
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2014 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/30/2014 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 06/30/2014 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/07/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The water heater schedule has water heater with an input of 199,000 BTU per hour while the gas schematic shows a storage water heater with an input of 300 CFH. Lined water heaters with a heat input of 200,000 BTU per hour or more, an operating water temperature of 210ยบ F or greater, or a nominal water containing capacity of 120 gallons or more are required to comply with the rules contained in Article 4 (Arizona Boilers and Lined Hot Water Heaters) of the Arizona Administrative Code. http://www.azsos.gov/public_services/Title_20/20-05.htm#ARTICLE_4. 2. Correct the gas pipe sizing calculations, demonstrating conformance to Section 402.1 and 402.3, IFGC 2012. 3. Section 2902.2, IBC 2012 requires that separate toilet facilities be provided for each sex in occupancies with 15 or more occupants. In addition, for public toilet facilities, the required lavatory shall be located in the same room as the water closet. Revise the design of the toilet facilities. Reference: Section 405.3.2, IPC 2012. 4. Verify the pressure drop due to the reduced pressure backflow preventer and revise the water pressure calculations as required. Reference: Section 604.1, IPC 2012. 5. The direct-connection of water to an appliance (e.g. beverage dispenser, coffee brewer, tea brewer, misting system, etc.) shall be protected against backflow. Specify the device to be used for the appliance connection. Reference: Sections 608.1 through 608.16, IPC 2012. 6. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 7. The drawings indicate that six fixtures (4 floor sinks, 1 hand sink, and 1 mop sink) are connected to the hydromechanical grease interceptor. Verify that the Regional Wastewater Reclamation Department will allow this. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson. 8. The scheduled model of the hydromechanical grease separator is not PDI-certified. Provide documentation showing that the scheduled hydromechanical grease separator meets the testing and listing requirements of Section 1003.3.4, IPC 2012. 9. Show how the external flow control device for the hydromechanical grease separator is to be installed below the floor level and accessible in accordance with the manufacturer's instructions. Reference: Section 1003.4.2, IPC 2012. 10. Provide a vent downstream of the hydromechanical grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2012. |
| 07/07/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the keynotes shown on sheet M1.0: numbers 1, 2, and 3 don't appear to apply to the current activity and keynotes 4 and 5 are not shown on the drawings. Reference: Section 107.2.1, IBC 2012. 2. Clarify the purpose of the Split System A/C Heat Pump Schedule shown on sheet M2.0. Reference: Section 107.2.1, IBC 2012. 3. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. 4. Ventilation calculations for HVAC systems supplying multiple zones shall take into account the different occupancy loads in each zone. Reference: Section 403.3.2.3, IMC 2012. 5. Food service drawings are shop drawings; design criteria (e.g. materials, dimensions, exhaust quantities, and installation criteria) for a Type I hood and exhaust system are to be determined by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 6. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012. 7. Show that the hood installation complies with Section 507.9, IMC 2012 for clearances. The installation of a 1-hour fire-rated assembly between combustible construction and a Type I hood does not reduce the separation requirement to 3". |