Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM03541
Parcel: 117050890

Address:
340 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03541
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2014 MARTIN BROWN FIRE REVIEW Denied Sheet a0.2 makes extensive reference to a fire sprinkler system. Our records indicate no existing sprinkler system. Please clarify intent as to the installation of a system. If a sprinkler system is to be installed, this should be included on sheet a0.1 under deferred submittals.
A kitchen exhaust hood fire suppression system must be installed in a type 1 hood. Please include this under deferred submittals on sheet a0.1.
06/17/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Wall switch indicated for restroom fans results in a violation of the mechanical code (recirculation of air when ef is off but a/c is on). Indicate that EF1 and EF2 are to be switched through time clock set to all hours that business is open.
2) Errata: IECC compliance information pp e4.0 did not properly copy onto plan sheet. Provide the information on separate sheets or clean up copy.
3) Errata: PP e2.0 general note 23 references the 2005 NEC.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
06/18/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) This is an A2 occupancy, or possibly an F1 but it is not Retail. Change occupancy classification to match actual occupancy type.
2) Restrooms are not considered occupiable space and should not be included in your occupant load calculations
3) Recalculate occupant loads per Table 1004 of the IBC
4) Corrected occupant load calculations may require 2 exits.
5) Door 110A is to swing in direction of egress, a two way swing could interfere with emergency egress.
6) Provide clearance on the latch side of door 110A in compliance with ANSI 117.1 table 404.2.3.2
7) Provide landing and accessible handrails at second exit to rear.
8) Plans indicate that the building is fully sprinklered for fire suppression. If it is not then you should remove all notes about fire suppression.
9) If there is no fire suppression, then it is likely that the exit corridor shall have to be fire rated.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
06/24/2014 ROBERT SHERRY WATER REVIEW Completed
06/24/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review Revised drawings to be delivered on 6/26/14
06/25/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review Revised drawings to be delivered on 6/26/14

Final Status

Task End Date Reviewer's Name Type of Review Description
06/30/2014 CPIERCE1 REJECT SHELF Completed