Permit Number: T14CM03540
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03540
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2014 STEVE SHIELDS ZONING REVIEW Approved
06/10/2014 JASON GREEN ENGINEERING REVIEW Approved
06/11/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/11/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. Provide structural details to show how the fan coil unit is to be connected to the building structure. Reference: Section 302.1, IMC 2012.
3. Provide the kiln manufacturer's equipment data and installation instructions for the new kilns. Reference: Sections 301, 304.1, and 923.1.1, IMC 2012.
4. Provide listing information for the CPVC exhaust duct. Reference: Sections 301, and 304.1, IMC 2012.
5. Clarify the location of the exhaust discharge for the kilns relative to walk ways and building openings. Reference: Sections 501.3.1 and 501.3.1.1, IMC 2012.
6. Verify that there is adequate make-up air (supply air, transfer air, or outside air) for the kiln exhaust to maintain the room with a neutral or slightly negative pressure. Reference: Section 501.4, IMC 2012.
7. Verify that the exhaust duct is not located within a return air plenum. Reference: Sections 601.4 and 602.2.1, IMC 2012.
06/11/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/11/2014 ROBERT SHERRY WATER REVIEW Approved
06/11/2014 MARTIN BROWN FIRE REVIEW Denied Please provide cut sheets and manufacturer's instructions for kilns.
06/11/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/12/2014 LHANLY1 WWM REVIEW Passed
06/12/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed