Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM03512
Parcel: 117040950

Address:
604 N 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM03512
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2014 KEN BROUILLETTE FIRE REVIEW Approved
08/05/2014 ROBERT SHERRY WATER REVIEW Completed
08/05/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Verify the scope of work for this activity. On sheet A1.2, the kitchen is noted as being separately permitted and no kitchen drawings have been included in this drawing set but the mechanical and plumbing designs appear to include the kitchen installation. Reference: Section 107.2.1, IBC 2012.]
2. Revise the code statement to indicate "local amendments"; there are no State amendments. [Initial comment: The International Plumbing Code, 2012, is the controlling code for this activity, not the 2006 International Plumbing Code (see Section 15000, sheet M9.6). Reference: Section 101, IBC 2012.]
3. Revise riser diagram 1/M8.2 to show the vent located downstream of the grease interceptor. [Initial comment: Provide a vent downstream of the proposed grease interceptor (note the proposed model has an integral flow control plate and does not require an additional exterior flow control device). Reference: Sections 1003.3.5 and 1003.9, IPC 2012.]
4. Clarify the plan for the gas service to the basement. On sheet M3.10 the gas pressure is regulated down to 11" WC and the pipe sized for a maximum pressure drop of 0.3" WC (Table 402.4(1), IFGC 2012). On sheet M3.7, the gas is delivered to appliances G30 and G32 and another pressure regulator is installed at each appliance to further reduce the gas pressure. What is the actual pressure required for the two appliances and how are the regulators in the basement to be vented? Note that using Table 402.4(1) at a developed length of 250-feet, G30 will require a 1-1/4" supply and G32 will require a 1-1/2" supply. [Initial comment: If the natural gas is being delivered with a maximum pressure drop of 0.5" WC, revise the size of the natural gas pipe serving the appliances, G30 and G32 per Table 402.4 (2). Reference: Section 402.4, IFGC 2012.]
08/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change To avoid the need for an economizer, the EER for HP-8 must be at least 12.1, a 10% increase over the minimum EER of 11.0 (Table C403.2.3 (2)). The schedule shows an EER of 11.7. [Initial comment: HP-8, with an EER of 11.6, does not meet the required efficiency increase to avoid the need for an economizer, Section 403.3.1 (exception 6), IECC 2012.]
08/08/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed