06/24/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 6-24-14
Activity: T14CM03481
Address: 114 E. Palmdale
Applicant: Adept General Contracting

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. The City of Tucson has adopted the 2012 International family of codes. Correct references to the 2006 IRC and the 2005 NEC in the general notes on sheet G1.
2. Provide sheet S2 for review as referenced on sheet S1. Additional review comments may apply to information not previously provided.

SITE PLAN:
3. Specify the location of all utility lines and service meters, R106.1.1.

STRUCTURAL / FRAMING PLAN:
4. Specify joist size and series on framing plan for roof framing members.
5. Provide section detail for joists above non-bearing wall with appropriate space for deflection, R802.10.1(10) or include footing under interior bearing wall and squash blocking for mid-point bearing as required by I-joist manufacturer.

ELECTRICAL PLAN:
6. Provide riser diagrams for sub-panels with feeder conductors, conduit sizes, over-current protection (with appropriate correction factors) and grounding method E3607/8, E3705.5.
7. Provide feeder load calculations for sub-panels (40% demand factor may not be applied) and indicate primary service panel capacity, E3704.3.
8. Specify GFCI protection for receptacles located in storage area, E3902.2.
9. Indicate control mechanism for exterior lighting.

OUTDOOR LIGHTING CODE
10. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Model plans should specify a minimum lot size for the proposed exterior lighting.