Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM03461
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/31/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the specifications for the new HVAC units. 2. Provide heating/cooling load calculations for the new HVAC units. 3. Show that the new HVAC units comply with the requirements of Section C403, IECC 2012. |
| 07/31/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/07/2014 | ROBERT SHERRY | ELECTRICAL-COMMERCIAL | REVIEW | Passed | Electrical to A/C units to be provided as part of TI |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/07/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |