Permit Number: T14CM03461
Parcel: 13215024A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM03461
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/31/2014 KEN BROUILLETTE FIRE REVIEW Approved
07/31/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the specifications for the new HVAC units.
2. Provide heating/cooling load calculations for the new HVAC units.
3. Show that the new HVAC units comply with the requirements of Section C403, IECC 2012.
08/07/2014 ROBERT SHERRY ELECTRICAL-COMMERCIAL REVIEW Passed Electrical to A/C units to be provided as part of TI

Final Status

Task End Date Reviewer's Name Type of Review Description
08/07/2014 SHANAE POWELL OUT TO CUSTOMER Completed