Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM03432
Parcel: 126120880

Address:
4644 E HOLMES ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM03432
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T14CM03432
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Show the water pipe size between the water meter and point of connection for new plumbing.

SECTIONS - DETAILS:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
2. Calculate and show the attic ventilation using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation.
3. Provide access between attic spaces of a minimum 22" x 30" opening, R807.

PLUMBING PLANS:

1. Show the water service pipe size with sufficient capacity for controlling excessive flow rates, P2903.6. A minimum 1" service pipe is required for supplying water to more than 9.5 fixture units.
2. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance. Existing gas pipes may require upgrading when relocating the gas meter.

MECHANICAL PLANS:

1. Limit all code references to those recognized by the City of Tucson. Update the code reference shown on sheet M-1.
2. Show supply ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, N1103.2.1.
3. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Show a receptacle outlet within 3' of each lavatory basin in each bathroom, E3901.6.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2014 CPIERCE1 OUT TO CUSTOMER Completed