Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM03391
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/16/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Several sheets of this submittal have lettering smaller than the required COT minimum standard of 3/32" actual size for both upper and lower case. Please revise all non-compliant sheets and resubmit. SHEET A100 1. Insure accessibility clearances for the laundry rooms as required by ICC A117.1, Section 603 and 304.3. a. Show these clearances on the floor plan with all required dimensions. 2. At unit 20, the 5'-0" clearance circle is pushed rather far into the lavatory so much so that the knee clearance is hitting the bowl depth and the sink drain pipes. 3. Both toilet rooms in the Conference Room and Main Office must be accessible as per ICC A117.1, Section 1109.2. See exceptions for the main office toilet room. END OF REVIEW |
| 06/25/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/25/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the size of the water service line for the three buildings: based on the water calculations on sheet P200, it is undersized. Reference: Section 603.1, IPC 2012. 2. Provide cleanouts for all horizontal drains (see the showers in B/P200). Reference: Section 708.3.1, IPC 2012. |
| 06/25/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/27/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/30/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 06/30/2014 | CPIERCE1 | REJECT SHELF | Completed |