Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2014 MARTIN BROWN FIRE REVIEW Approved
06/16/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Several sheets of this submittal have lettering smaller than the required COT minimum standard of 3/32" actual size for both upper and lower case. Please revise all non-compliant sheets and resubmit.
SHEET A100
1. Insure accessibility clearances for the laundry rooms as required by ICC A117.1, Section 603 and 304.3.
a. Show these clearances on the floor plan with all required dimensions.
2. At unit 20, the 5'-0" clearance circle is pushed rather far into the lavatory so much so that the knee clearance is hitting the bowl depth and the sink drain pipes.
3. Both toilet rooms in the Conference Room and Main Office
must be accessible as per ICC A117.1, Section 1109.2. See exceptions for the main office toilet room.
END OF REVIEW
06/25/2014 ROBERT SHERRY WATER REVIEW Completed
06/25/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the size of the water service line for the three buildings: based on the water calculations on sheet P200, it is undersized. Reference: Section 603.1, IPC 2012.
2. Provide cleanouts for all horizontal drains (see the showers in B/P200). Reference: Section 708.3.1, IPC 2012.
06/25/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/27/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/30/2014 SHANAE POWELL OUT TO CUSTOMER Completed
06/30/2014 CPIERCE1 REJECT SHELF Completed