Permit Number: T14CM03292
Parcel: 11711096D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03292
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2014 LAITH ALSHAMI ENGINEERING REVIEW Approved
06/02/2014 ROBERT SHERRY WATER REVIEW Approved
06/02/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
06/02/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/02/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; WALL TYPES: WALL W7 INDICATES TO BRACE THE WALL AS REQUIRED. PROVIDE A DETAIL ON THE DRAWINGS INDICATING THE BRACING SIZE AND SPACING, AND THE CONNECTOR SIZE AND QUANTITY FOR CONNECTION OF THE BRACE TO THE TOP OF THE PARTITION AND TO THE EXISTING STRUCTURE ABOVE.
2. SHEET A1.0; ELEVATION 7: THE TOP OF THE COUNTER SHOULD INDICATE 2'-10" ABOVE THE FINISH FLOOR (FOR ACCESSIBILITY). REVISE.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/02/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/02/2014 STEVE SHIELDS ZONING REVIEW Approved
06/03/2014 MARTIN BROWN FIRE REVIEW Approved
06/03/2014 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/03/2014 SPOWELL1 WWM REVIEW Needs Review