Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/02/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/02/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012. |
06/02/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/02/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/02/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1.0; WALL TYPES: WALL W7 INDICATES TO BRACE THE WALL AS REQUIRED. PROVIDE A DETAIL ON THE DRAWINGS INDICATING THE BRACING SIZE AND SPACING, AND THE CONNECTOR SIZE AND QUANTITY FOR CONNECTION OF THE BRACE TO THE TOP OF THE PARTITION AND TO THE EXISTING STRUCTURE ABOVE. 2. SHEET A1.0; ELEVATION 7: THE TOP OF THE COUNTER SHOULD INDICATE 2'-10" ABOVE THE FINISH FLOOR (FOR ACCESSIBILITY). REVISE. 3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
06/02/2014 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
06/02/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/03/2014 | SPOWELL1 | WWM | REVIEW | Needs Review | |
06/03/2014 | SPOWELL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
06/03/2014 | MARTIN BROWN | FIRE | REVIEW | Approved |