Permit Number: T14CM03286
Parcel: 140291980

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM03286
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2014 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed; show the size of the water meter on the drawing. [Second comment: Show the size of the existing water meter.] [Initial comment: Show the location of the water meter and the reduced pressure backflow assembly on the drawings; indicate the sizes of the water meter and the backflow assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf]
07/21/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved; provide the water and the waste & vent isometrics of the new work. Place the water pressure calculations on the drawing. Note that the pressure drop across a reduced pressure zone backflow prevention assembly is not 5 PSI. [Second comment: Provide water isometrics along with waste and vent isometrics that include all of the pipe sizes. The waste and vent isometrics shall show how the new piping will be connected to the existing piping. Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply and sanitary waste systems to become overloaded.] [Initial comment: Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.]