Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM03286
Parcel: 140291980

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03286
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
06/02/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
06/02/2014 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/02/2014 ROBERT SHERRY WATER REVIEW Needs Review
06/02/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET X1.1; CODE ANALYSIS DATA: THE ACCESSIBILITY IS REFERENCED TO THE 2003 ICC/ANSI OR THE 2010 ADA. REMOVE THE ADA REFERENCE AND REVISE THE ICC/ANSI TO THE 2009 EDITION.
2. SHEET A1.1N; FLOOR PLAN: NOTE 2 INDICATES THE REMOVAL OF EXISTING URINALS. SINCE NO FIXTURE COUNT IS PROVIDED IN THE CODE ANALYSIS, ARE THE REQUIREMENTS FOR FIXTURES MET FOR BOTH SEXES. VERIFY.
3. GENERAL: ON THE DRAWINGS, PROVIDE A DETAIL INDICATING THE BRACING OF THE NEW INTERIOR PARTITIONS MEETS THE IBC SECTION 1607.14. INDICATE THE BRACING SIZE AND SPACING, AND THE CONNECTION SIZES AND QUANTITIES FOR THE BRACE TO THE TOP OF THE PARTITION AND TO THE EXISTING STRUCTURE ABOVE.
4. SHEET A9.2; ENLARGED PLAN 9 (NOTE 2): IF THE DEPTH OF THE PANELS ARE GREATER THAN 24", THE CLEAR WIDTH BETWEEN PANELS MUST BE 36" (SEE ICC/ANSI A117.1-2009 FIGURE 305.7a). VERIFY.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/02/2014 FRODRIG2 WWM REVIEW Passed
06/02/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
06/02/2014 LAITH ALSHAMI ENGINEERING REVIEW Approved
06/02/2014 KEN BROUILLETTE FIRE REVIEW Approved
06/02/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed