Permit Number: T14CM03283
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03283
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEETS G1.0 THROUGH A6.0: PROJECT MUST BE STAMPED BY A LICENSED PROFESSIONAL REGISTERED IN THE STATE OF ARIZONA. PROVIDE.
2. SHEET A1.0; DOOR HARDWARE NOTES-ADA: REFERENCE IS TO ADA STANDARDS. REVISE TO THE ICC/ANSI A117.1-2009 EDITION FOR ACCESSIBLE STANDARDS.
3. SHEET A1.0; PARTITION TYPE "C": PROVIDE A CONNECTION ON THIS DETAIL OF THE NEW FUR OUT STUDS TO THE SALES/STOCK PARTITION.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/02/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
06/02/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/02/2014 ROBERT SHERRY WATER REVIEW Approved
06/02/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/02/2014 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
06/12/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
06/12/2014 LOREN MAKUS ENGINEERING REVIEW Approved
06/13/2014 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/13/2014 SPOWELL1 FIRE REVIEW Needs Review