Permit Number: T14CM03281
Parcel: 12621001C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03281
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2014 STEVE SHIELDS ZONING REVIEW Approved
06/02/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/02/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
06/02/2014 ROBERT SHERRY WATER REVIEW Approved
06/02/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1; CODE ANALYSIS DATA: REVISE THE ACCESSIBILITY CODE TO THE 2009 ICC/ANSI, AND REMOVE THE REFERENCE TO THE ADA.
2. SHEET TS1; CODE STUDY: THE GROSS USABLE AREA IS LISTED AT 17,012 SF, BUT THE OCCUPANCY LOAD IS BASED ON 17,715 SF. CLARIFY.
3. SHEET TS1; GENERAL SITE NOTES: NOTE 2 REFERENCES THE 2003 ADA FOR ACCESSIBILITY. REMOVE THAT REFERENCE.
4. SHEETS D1 AND A1; KEY NOTES: NOTES D4.3 AND D5.1 ARE THE SAME. REVISE.
5. SHEET D1; KEY NOTES: ADD NOTE D6.2.
6. SHEET A1; PARTITION TYPES: PARTITION TYPE 4B WILL REQUIRE A DETAIL ON THE DRAWINGS INDICATING BRACE SIZE AND SPACING, AND THE CONNECTION SIZE AND QUANTITY AT THE TOP OF THE PARTITION AND TO THE EXISTING STRUCTURE ABOVE.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/02/2014 LAITH ALSHAMI ENGINEERING REVIEW Approved
06/02/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a design for the mounting shelfs for water heaters WH-1 and WH-2 along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012.
06/02/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/03/2014 MARTIN BROWN FIRE REVIEW Approved
06/11/2014 FRODRIG2 WWM REVIEW Passed