Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2014 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T14CM03226
3320 N Martin Avenue
Residential (1st Review)

TRANSMITTAL DATE: May 30, 2014

The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

There is a carport shown on the most current aerial photos that is not shown on the plot plan. It appears this carport was built under permit #T09CM00839, show this carport on the plot plan.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/02/2014 LOREN MAKUS ENGINEERING REVIEW Denied Provide a complete and accurate plot plan.
06/11/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T14CM03226
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FOUNDATION PLANS:

1. The minimum footing depth below the undisturbed ground surface is 12", R403.1. The F-1 & F-3 foundation details at B/3.1 show acceptable, but possibly excessive depths.

FLOOR PLANS:

1. Clarify keynote #k sheet 0.3, R106.1.1.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R317.1 item 5. Clarify detail #C/7.1.
2. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.

PLUMBING PLANS:

1. Show a plumbing code recognized by the City of Tucson, 2012 IRC. Update 7th note under 15400 Plumbing.
2. Provide a revised fixture unit schedule using 2012 code values for verifying the required service pipe diameter, Table P2903.6. Those shown are not consistent with current codes.
3. Clarify the pipe diameter at the point of connection of the new cold water line to existing service pipes. Existing water pipes may require replacement with larger sizes for controlling excessive water flow rates, P2903.7.
4. Show hot water pipe with minimum R-3 insulation, N1103.4.2.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3703.5. Clarify the bathroom receptacle and exterior circuits as they may not be on the same circuit.
3. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other room/locations, E3703.4.
4. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC equipment, E3901.12.
5. Protect all 15A & 20A proposed outlets (except bathrooms and kitchen) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.
6. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.13.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13, N1102.1. Update the U=0.75 valves on sheet 0.1.