Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM03217
Parcel: 123080540

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03217
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
05/29/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/29/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
05/29/2014 ROBERT SHERRY WATER REVIEW Approved
05/29/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/29/2014 JASON GREEN ENGINEERING REVIEW Approved
05/29/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/29/2014 MARTIN BROWN FIRE REVIEW Approved
05/29/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/04/2014 CPIERCE1 WWM REVIEW Completed