Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM03195
Parcel: 13323164A

Review Status: Completed

Review Details: REVISION - - 7TH

Permit Number - T14CM03195
Review Name: REVISION - - 7TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET SP1; SITE PLAN 1: THE NEW PRECAST BOLLARD REFERENCES DETAIL 9-SP2. PLEASE REVISE THE REFERENCE.
2. SHEET SP1; PLANS 2A AND 2B: THE NEW PRECAST BOLLARD REFERENCES DETAIL 9-SP2. PLEASE REVISE THE REFERENCE. THESE REFERENCES ARE CIRCLED IN RED ON THE LATEST SHEET SP1.
06/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2016 RBENT1 APPROVAL SHELF Completed
06/09/2016 RBENT1 OUT TO CUSTOMER Completed