Review Details: REVISION - - 7TH

Permit Number - T14CM03195
Review Name: REVISION - - 7TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET SP1; SITE PLAN 1: THE NEW PRECAST BOLLARD REFERENCES DETAIL 9-SP2. PLEASE REVISE THE REFERENCE.
2. SHEET SP1; PLANS 2A AND 2B: THE NEW PRECAST BOLLARD REFERENCES DETAIL 9-SP2. PLEASE REVISE THE REFERENCE.
04/13/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. Plan sheet E4.3 shows a new load center "LTS1". Is this part of this revision. Not addressed by Narrative. Please provide all necessary information associated with this load center in order to provide a complete plan review.
Ref: IBC 107.2.1
06/07/2016 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/08/2016 RBENT1 APPROVAL SHELF Completed
06/08/2016 RBENT1 OUT TO CUSTOMER Completed