Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 7TH
Permit Number - T14CM03195
Review Name: REVISION - - 7TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET SP1; SITE PLAN 1: THE NEW PRECAST BOLLARD REFERENCES DETAIL 9-SP2. PLEASE REVISE THE REFERENCE. 2. SHEET SP1; PLANS 2A AND 2B: THE NEW PRECAST BOLLARD REFERENCES DETAIL 9-SP2. PLEASE REVISE THE REFERENCE. |
| 04/13/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. #1. Plan sheet E4.3 shows a new load center "LTS1". Is this part of this revision. Not addressed by Narrative. Please provide all necessary information associated with this load center in order to provide a complete plan review. Ref: IBC 107.2.1 |
| 06/07/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/08/2016 | RBENT1 | APPROVAL SHELF | Completed |
| 06/08/2016 | RBENT1 | OUT TO CUSTOMER | Completed |