Permit Number: T14CM03195
Parcel: 13323164A

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T14CM03195
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
08/12/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/12/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/12/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the plumbing fixture schedule for fixture L10. A thermostatic mixing valve is shown in the accessories section, but is noted as "not required for L6, L8, [and] L10". Tempered water is required to be provided for lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/01/2015 EGALLET1 OUT TO CUSTOMER Completed