Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T14CM03195
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/26/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/06/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/06/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/08/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide additional information for (MSB) switchboard section addition as indicated per Plan Sheet E1 and E2.4 and E4. Verify with manufacturer of equipment that this will not compromise the listing and may require a field inspection / certification by an NRTL. Ref: NEC 110.3 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/27/2015 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |