Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM03195
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/29/2014 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | ENG can not approve the development plan package until approval of the DP Package DP14-0018. Provide a copy of the approved DP Package for building plan approval. JG |
05/30/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Walmart Expansion - 7150 E. Speedway Blvd. T14CM03195 Building Plan (1st Review) TRANSMITTAL DATE: May 30, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans but cannot approve until development package, DP13-0230 has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
06/03/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
06/10/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | STRUCTURAL 1. Provide bearing capacities especially for the shallow foundations. 2. Provide geo-technical report 3. Provide key plan for structural foundations. 4. Provide certification of the special inspectors. A two part form is available on our web site. END OF REVIEW |
06/12/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths on plans. Reference: Section 402.3, IFGC 2012. 2. Show how backflow protection is being provided for the make-up water for the evaporative condenser. Reference: Sections 608.1 and 608.16.7, IPC 2012. 3. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012. |
06/13/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. 2. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012. 3. Revise the sequence of operation for the restroom exhaust fan EF4 (Pharmacy Toilet) so that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. 4. Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012. |
06/18/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide available fault currents, and bracing informtion for new panels. Verify that existing equipment will be properly braced for new available fault currents |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/11/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
07/11/2014 | CPIERCE1 | REJECT SHELF | Completed |