Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM03195
Parcel: 13323164A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM03195
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2014 JASON GREEN ENGINEERING REVIEW Reqs Change ENG can not approve the development plan package until approval of the DP Package DP14-0018. Provide a copy of the approved DP Package for building plan approval. JG
05/30/2014 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Walmart Expansion - 7150 E. Speedway Blvd.
T14CM03195
Building Plan (1st Review)

TRANSMITTAL DATE: May 30, 2014

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans but cannot approve until development package, DP13-0230 has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/03/2014 KEN BROUILLETTE FIRE REVIEW Approved
06/10/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change STRUCTURAL
1. Provide bearing capacities especially for the shallow foundations.
2. Provide geo-technical report
3. Provide key plan for structural foundations.
4. Provide certification of the special inspectors. A two part form is available on our web site.
END OF REVIEW
06/12/2014 ROBERT SHERRY WATER REVIEW Completed
06/12/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths on plans. Reference: Section 402.3, IFGC 2012.
2. Show how backflow protection is being provided for the make-up water for the evaporative condenser. Reference: Sections 608.1 and 608.16.7, IPC 2012.
3. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012.
06/13/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
3. Revise the sequence of operation for the restroom exhaust fan EF4 (Pharmacy Toilet) so that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
4. Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
06/18/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide available fault currents, and bracing informtion for new panels.

Verify that existing equipment will be properly braced for new available fault currents

Final Status

Task End Date Reviewer's Name Type of Review Description
07/11/2014 SHANAE POWELL OUT TO CUSTOMER Completed
07/11/2014 CPIERCE1 REJECT SHELF Completed