Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T14CM03155
Parcel: 12213072C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM03155
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2014 RONALD BROWN ADA REVIEW Passed
09/03/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Minimum font size for plans submitted to the City of Tucson is 3/32" for all upper and lower case lettering. Rework electrical pages to meet this standard.
2) The applicable electrical code is the 2011 NEC. Modify all code references to reflect that edition.
3) There are references to DC grounding electrode conductors ahead of the inverters on the 3-line diagram. Please clarify.
4) Technical information provided for the inverter is incomplete. Clarify that the AC equipment grounding conductor is not internally connected at the inverter to the DC GEC terminal. It is not unusual for this connection to be on a common buss, or internally bonded for UL 1741 listed equipment.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
09/04/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Clarify fire department access paths on roof of existing building. Provide dimensions. Reference International Fire Code section 605.11.3.3.
2) Specify racking system on plans.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
09/04/2014 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/05/2014 MARTIN BROWN FIRE REVIEW Denied Some notes on side of layout plan were cut off. Please rectify.
Also, it appears there is no way for firefighters to access large ares of the roof for ventelation purposes in the event of a fire. Please review section 605 of the 2012 International Fire Code and indicate how access requirements are being accomplished.
09/29/2014 LOREN MAKUS ENGINEERING REVIEW Denied Please see the comments for the floodplain use permit.
The floodplain use permit must be approved before this permit can be approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2014 CPIERCE1 OUT TO CUSTOMER Completed