Permit Number: T14CM03073
Parcel: 11706195A

Address:
33 S 6TH AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T14CM03073
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. DOES THIS REVISION 2 HAVE ANYTHING TO DO WITH THIS PORTION OF THE BUILDING? VERIFY.
10/29/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Could not locate keynote 52 delta 8 revision on sheet e2.0
2) Could not locate keynote 38 delta 8 revision on sheet e2.0
3) PP e3.0 shows SES 1 with overhead drop but notes indicate it is going to be fed from new transformer. Which is it?


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed