Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T14CM03073
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. DOES THIS REVISION 2 HAVE ANYTHING TO DO WITH THIS PORTION OF THE BUILDING? VERIFY. |
| 10/29/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal. 1) Could not locate keynote 52 delta 8 revision on sheet e2.0 2) Could not locate keynote 38 delta 8 revision on sheet e2.0 3) PP e3.0 shows SES 1 with overhead drop but notes indicate it is going to be fed from new transformer. Which is it? If there are questions regarding this review contact: LeeRay 520-837-4906 LeeRay.Hanly@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/06/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |