Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/29/2014 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Reqs Change Use the correct type of backflow preventer for the calculations; a double check valve is not allowed for protecting the municipal water supply from this building. [Second comment: No specification sheets were included in this submittal but since the first check valve for a reduced pressure backflow preventer is required to have a 5 PSI pressure drop, it is unlikely that you will find a reduced pressure backflow preventer that has a 5 PSI pressure drop across two check valves and a reduced pressure zone.] [Initial comment: The water pressure calculations include a 5 PSI pressure drop due to the reduced pressure backflow preventers. Provide specification sheets from the manufacturer that supports that pressure drop. Reference: Section 604.1, IPC 2012.]
08/29/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed