Permit Number: T14CM03072
Parcel: 117061910

Address:
11 S 6TH AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T14CM03072
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1.1; DETAIL 02: NOTE 4 INDICATES A HOLDOWN, AND A BOXED NOTE INDICATES TO SEE THE GENERAL STRUCTURAL NOTES SHEAR WALL SCHEDULE. NOTHING WAS FOUND IN THE NOTES OR DETAILS THAT INDICATED HOLDOWN SIZES. CLARIFY.
2. SHEET S2.1; FOUNDATION KEYNOTES: ADD TO NOTE 11 THAT IF THE EXISTING WALL OR FOOTING DO NOT MEET THE STATED CRITERIA, TO CONTACT THE PROJECT ARCHITECT OR STRUCTURAL ENGINEER.
3. SHEET S2.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEET 2): THE CALCULATIONS INDICATE COLUMN C5 AS (2) 2X6, WHILE THE COLUMN SCHEDULE INDICATES A 4X4. CLARIFY.
4. SHEET S2.1; FOUNDATION KEYNOTES: NOTE 1 INDICATES IT IS NOT USED, BUT IT IS SHOWN IN THREE LOCATIONS ON THE PLAN. CLARIFY.
5. SHEET S2.2 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 1): THE CALCULATIONS INDICATE A BEAM B4 ON THE SOUTH WALL, BUT THIS BEAM IS NOT SHOWN ON THE FRAMING PLAN. CLARIFY.
6. SHEET S3.0; DETAIL 113: REVISE NOTE 3 TO A CONTINUOUS 2X PLATE (SEE DETAIL 114).
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2014 AROMERO4 REJECT SHELF Completed