Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM02947
Parcel: 13106008A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02947
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2014 DAVID RIVERA ZONING REVIEW Approved
05/19/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1) Clarify amperage rating and voltage of service entrance
2) Provide new and existing loads on service.
3) Specify disconnects for new feeders to pnl k
4) Specify feeders and conduit to pnl k
5) Justify 10K AIC rating for pnl K
6) All 120v kitchen plug receptacles to be GFCI protected.
05/19/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change Needs structural calculations for the new type 1 exhaust hood and hvac roof top units.
05/19/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/27/2014 SPOWELL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
05/27/2014 SPOWELL1 PLUMBING-COMMERCIAL REVIEW Needs Review
05/27/2014 SPOWELL1 WATER REVIEW Needs Review
05/27/2014 SPOWELL1 FIRE REVIEW Needs Review
05/27/2014 SPOWELL1 WWM REVIEW Needs Review
05/27/2014 SPOWELL1 ENGINEERING REVIEW Needs Review