Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM02947
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
05/19/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1) Clarify amperage rating and voltage of service entrance 2) Provide new and existing loads on service. 3) Specify disconnects for new feeders to pnl k 4) Specify feeders and conduit to pnl k 5) Justify 10K AIC rating for pnl K 6) All 120v kitchen plug receptacles to be GFCI protected. |
05/19/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Needs structural calculations for the new type 1 exhaust hood and hvac roof top units. |
05/19/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/27/2014 | SPOWELL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
05/27/2014 | SPOWELL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
05/27/2014 | SPOWELL1 | WATER | REVIEW | Needs Review | |
05/27/2014 | SPOWELL1 | FIRE | REVIEW | Needs Review | |
05/27/2014 | SPOWELL1 | WWM | REVIEW | Needs Review | |
05/27/2014 | SPOWELL1 | ENGINEERING | REVIEW | Needs Review |