Review Details: COMMERCIAL - TI

Permit Number - T14CM02946
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
05/19/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify the exhaust air flow rate and sequence of operation. The minimum exhaust rate is 50 CFM per water loset or urinal with continuous operation, 70 CFM per water closet or urinal with intermittant operation.
2. Show the size of the proposed dryer vent.
3. Show the specifications for the proposed exhaust fan in the laundry room.
05/19/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1) Provide panel schedule A with new loads added. Also specify circuits, loads and wire sizes

2) Provide IECC lighting compliance information for rooms 103, 108, 120.
05/19/2014 ROBERT SHERRY WATER REVIEW Reqs Change Verify the presence of a backflow preventer at the water meter and the size of the water meter.
05/19/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Completed
05/19/2014 LHANLY1 WWM REVIEW Passed
05/19/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The fixture drain for a clothes washer shall connect to a horizontal drain at least 3" in size.
2. Show the existing DWV piping to clarify how the addition of the urinal is to be accomplished.
3. Provide water hammer arrestors for the clothes washer connections.
05/19/2014 LAITH ALSHAMI ENGINEERING REVIEW Approved
05/19/2014 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/27/2014 SPOWELL1 FIRE REVIEW Needs Review