Permit Number: T14CM02882
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02882
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
05/16/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/16/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
05/16/2014 ROBERT SHERRY WATER REVIEW Approved
05/16/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A2.1; SHEET MP2.1: COORDINATE THE SUPPORT OF THE NEW WATER HEATER ON THESE TWO SHEETS.
2. SHEET A2.1; SHEET MP2.1: PROVIDE A DETAIL OF THE CONNECTION OF THE WATER HEATER SUPPORT TO THE STRUCTURE ABOVE.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/16/2014 JASON GREEN ENGINEERING REVIEW Approved
05/16/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the height and method of support for the water heater.
05/16/2014 MARTIN BROWN FIRE REVIEW Approved
05/21/2014 AROMERO4 WWM REVIEW Completed