Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM02753
Parcel: 10511043B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02753
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
05/12/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/12/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
05/12/2014 ROBERT SHERRY WATER REVIEW Approved
05/12/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; CEILING PLAN KEYNOTES: NOTE 3 WAS NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET A1; SECTION 7: AT THE STEEL STUD KICKERS ABOVE THE CEILING, PROVIDE THE KICKER SIZE. INDICATE THE CONNECTORS (SIZE AND QUANTITY) FOR THE CONNECTION OF THE KICKER TO THE TOP OF THE PARTITION. ADD TO THE SECTION, INCLUDING THE CONNECTION OF THE KICKER TO THE EXISTING STRUCTURE ABOVE.
3. SHEET AA: REVISE THE SHEET NUMBER TO MATCH THE DRAWING INDEX (AA OR A1?).
05/12/2014 LHANLY1 WWM REVIEW Passed
05/12/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
05/12/2014 LAITH ALSHAMI ENGINEERING REVIEW Approved
05/12/2014 KEN BROUILLETTE FIRE REVIEW Approved
05/12/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed