Permit Number: T14CM02728
Parcel: 124150150

Address:
820 S EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM02728
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2014 MARTIN BROWN FIRE REVIEW Denied PLEASE PROVIDE CODE REVIEW ANALYSIS, INCLUDING
OCCUPANCY CLASSIFICATIO, OCCUPANT LOAD, EXITING, ETC
06/13/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET X1; SITE PLAN: WHAT DOES THE HEAVY LINE ON THE EAST WALL OF THE 4800 SF BUILDING DENOTE? VERIFY.
2. SHEET X1; SITE PLAN: IN THE EXISTING RECYCLING BUILDING, WHAT DO THE 14' AND 3' DIMENSIONS ON THE WEST WALL DENOTE? VERIFY.
3. SHEET X1: PROVIDE A CODE ANALYSIS FOR THE NEW BUILDINGS (USE, SIZE, CONSTRUCTION, ETC).
4. SHEET X1; DRAWING INDEX: A NOTE INDICATES A SOIL REPORT IS INCLUDED IN THIS SUBMITTAL. PROVIDE FOR REVIEW.
5. SHEET S2.0; BOXED NOTES: NOTE 1 INDICATES THE FOUNDATION DESIGN IS BASED ON ANTICIPATED FRAME REACTIONS AND LAYOUT PROVIDED BY THE METAL BUILDING MANUFACTURER. IS THAT NOTE PERTINENT TO THIS PROJECT SINCE THE METAL BUILDING MANUFACTURER HAS ALREADY PROVIDED REACTIONS AND LAYOUT? VERIFY.
6. METALLIC BUILDING COMPANY SHOP DRAWINGS; 40' X 120' BUILDING (SHEET E1): REVISE THE INDEX TO INCLUDE SHEETS R15 AND R16.
7. GENERAL: ARE THERE NO ARCHITECTURAL DRAWINGS OR SPECIFICATIONS THAT ARE REQUIRED ON THIS PROJECT? VERIFY.
8. GENERAL: PROVIDE TWO SETS OF THE METALLIC BUILDING COMPANY SHOP DRAWINGS FOR EACH BUILDING.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO EACH REVIEW COMMENT.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2014 CPIERCE1 REJECT SHELF Completed