| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/29/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Calculation of the required minimum ventilation rate for air handlers serving multiple zones requires the balancing data (supply CFM) for each zone and the calculations described in Sections 403.3.2.3.1 through 403.3.2.3.4, IMC 2012. Reference: section 403.3.2.3, IMC 2012. |