Permit Number: T14CM02678
Parcel: 117110990

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02678
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2014 STEVE SHIELDS ZONING REVIEW Approved
05/15/2014 JASON GREEN ENGINEERING REVIEW Approved
05/15/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
05/16/2014 MARTIN BROWN FIRE REVIEW Denied PER SECTION 1103.7.1 OF THE 2012 INTERNATIONAL FIRE CODE, A FIRE ALARM SYSTEM IS REQUIRED. PLEASE REVISE PLANS TO INDICATE ONE WILL BE INSTALLED.
05/16/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/16/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; show how each room is supplied with outside air. The current code is the 2012 IMC, not the 2009 IMC. [Initial comment: Show that the three new rooms have been provided with adequate ventilation. Reference: section 403.3, IMC 2012.]