Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/15/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
05/15/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
05/15/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
05/16/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | PER SECTION 1103.7.1 OF THE 2012 INTERNATIONAL FIRE CODE, A FIRE ALARM SYSTEM IS REQUIRED. PLEASE REVISE PLANS TO INDICATE ONE WILL BE INSTALLED. |
05/16/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/16/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; show how each room is supplied with outside air. The current code is the 2012 IMC, not the 2009 IMC. [Initial comment: Show that the three new rooms have been provided with adequate ventilation. Reference: section 403.3, IMC 2012.] |