Permit Number: T14CM02678
Parcel: 117110990

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02678
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T-100.00: PROVIDE A CODE ANALYSIS ON THIS SHEET, ALONG WITH PERTINENT INFORMATION AS REQUIRED BY THE IBC SECTION 107.
2. SHEET T-100.00; COMPLIANCE DIAGRAMS (WATER CLOSETS): PROVIDE A VERTICAL GRAB BAR PER THE ICC/ANSI A117.1-2009, FIGURE 604.5.1.
3. SHEET T-100.00; COMPLIANCE DIAGRAMS: VERIFY THE REQUIREMENTS OF THE ICC/ANSI A117.1-2009 ARE MET IN THESE DIAGRAMS.
4. SHEET T-100.00; CONSTRUCTION CLASSIFICATION: REFERENCE IS MADE TO TABLE 3-4. WHERE IS THIS TABLE? VERIFY.
5. SHEET T-100.00: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE COMPLIANCE DIAGRAMS DIMENSIONS.
6. SHEET A-100.00: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE.
7. SHEET A-100.00; HATCH KEY: IT IS HARD TO TELL WHICH WALLS ARE EXISTING (TO BE REMOVED) AND WHICH WALLS ARE EXISTING (TO REMAIN). CLARIFY.
8. GENERAL: ALL DRAWINGS MUST BE SEALED, SIGNED, AND DATED BY A DESIGN PROFESSIONAL REGISTERED IN THE STATE OF ARIZONA, AS REQUIRED BY THE IBC SECTION107.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the three new rooms have been provided with adequate ventilation. Reference: section 403.3, IMC 2012.
05/08/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Plans are required to be sealed by a registrant in the State of Arizona.
2) Minimum font size for all upper and lower case letters to be 3/32" per City of Tucson submittal requirements
3) Clarify extent of work. On demolition plan is it your intent to remove the plug receptacles noted as "new"…or is this a power plan and not a demo plan?
4) If there are new outlets to be installed then indicate circuiting.
5) Clarify extent of work in reflected ceiling plan. Are fixtures new or existing? Coordinate lighting symbols on reflected ceiling plan with symbol chart.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov Plan
05/08/2014 ROBERT SHERRY WATER REVIEW Approved
05/08/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/08/2014 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
05/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/15/2014 CPIERCE1 ENGINEERING REVIEW Needs Review
05/15/2014 CPIERCE1 ZONING REVIEW Needs Review
05/15/2014 CPIERCE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2014 CPIERCE1 OUT TO CUSTOMER Completed