Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM02639
Parcel: 124080390

Address:
315 N CHERRY AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM02639
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2014 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Reqs Change T14CM02639
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Show the address number on each floor plan. These identification numbers will also appear on the building and electrical panels.

FLOOR PLANS:

1. Show dwelling unit separation by a 1-hour firewall from floor to bottom of roof sheathing. Update note #7 sheet #2 showing compliance with R302.3 and replace "ceiling' with "roof". The fire rated barrier must include the attic area.
2. Provide a minimum 36" x 36" exterior landing at each door, R311.7.6. Stair steps are separate from the required landing. Update sheet #2.

SECTIONS - DETAILS:

1. Calculate and show the attic ventilation for each dwelling using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Each dwelling attic space requires separate gable vents.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. Show a source of heat within the new family room and existing bedroom #1. These rooms are not an extension of adjacent rooms.

ELECTRICAL PLANS:

1. Provide a panel schedule showing a description for each circuit to include a heating device for the new family room and existing bedroom #1, E3702.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2014 SHANAE POWELL OUT TO CUSTOMER Completed
11/06/2014 SHANAE POWELL REJECT SHELF Completed