Permit Number: T14CM02634
Parcel: 132150150

Address:
816 E EVANS BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02634
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2014 DAVID RIVERA ZONING REVIEW Approved
05/07/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Correct the ventilation calculations, verify the room areas.
2. The restroom exhaust fans shall run whenever the A/C unit supplies air to the restroom.
3. Show the size, route and termination of the condensate drains.
05/07/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Complete the water pressure calculations. Include the pressure drop due to the RPBP.
2. Clarify the fixture schedule - what fixtures will be remaining.
3. The specified faucet for the lavatories does not regulate the water temperature. Provide a mixing valve for each lavatory that is listed per ASSE 1070.
4. Verify the minimum flow rate required to activate the tankless water heaters.
5. What is the expansion tank for?
05/07/2014 ROBERT SHERRY WATER REVIEW Approved
05/07/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/07/2014 ELEIBOL1 ENGINEERING REVIEW Approved
05/07/2014 MARTIN BROWN FIRE REVIEW Approved
05/07/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/08/2014 CPIERCE1 WWM REVIEW Passed
05/08/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed Provide 2012 IECC (interior) lighting calculation: use ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination.