Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM02632
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the specified wter heater (and expansion tank) can be installed and maintained in the designated location. |
| 05/12/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A3.0: AT THE WATER HEATER SUPPORT, THE CONNECTION OF THE UNISTRUT SPANNING BETWEEN THE STEEL WALL STUDS SHOULD BE ADDED TO THE CALCULATIONS, INDICATING THE SIZE AND QUANTITY OF THE CONNECTORS. PROVIDE THAT INFORMATION ON SHEET A3.0. |
| 05/12/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/14/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |