Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM02604
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/09/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/09/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The load calculations appear to be for the entire suite, not just the area served by the two new heat pumps. The roof area used for the calculations is 6189 square feet but that area covered by the two new units is only about 2760 square feet. Coordinate the load calculations with the area served by the two new heat pumps or include the capacity of the existing units when justifying the new units. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the two new split systems specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.] |
| 06/10/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 06/13/2014 | SPOWELL1 | WWM | REVIEW | Needs Review |