Permit Number: T14CM02604
Parcel: 103090800

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02604
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
05/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the two new split systems specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
05/06/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.


1) Errata: Electrical code in code review is listed as 2012 NEC, revise to 2011 NEC
2) Errata: PP e1.0 keyed notes are not labeled.
3) PP e1.1 ComCheck lighting certificate did not print clearly, modify and ensure that font size meets minimum 3/32" requirement for City scanning purposes.
4) PP e3.0 Panel "N" ckt 20 identified as feeding lighting in conference room 101, verify as it is not indicated in lighting plans.






If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
05/06/2014 ROBERT SHERRY WATER REVIEW Approved
05/06/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET a2.0; DEMO KEYNOTES: NOTE 18 WAS NOT LOCATED ON THE PLAN. VERIFY.
2. SHEETS a3.0, a3.1, AND a4.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ROOM ID VERBIAGE AND DETAIL CUTS.
3. SHEET a3.1; FLOOR PLAN KEY NOTES: NOTES 5, 8, AND 13 WERE NOT LOCATED ON THE PLAN. VERIFY.
4. SHEET a4.0; KEY NOTES: NOTES 3, 5, AND 12 WERE NOT LOCATED ON THE PLAN. VERIFY.
5. GENERAL: PROVIDE A DETAIL FOR THE CONNECTION OF THE TOP OF THE PARTITIONS TO THE STRUCTURE ABOVE (ALL WALLS INDICATED FULL HEIGHT).
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/06/2014 LOREN MAKUS ENGINEERING REVIEW Approved
05/06/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp).
2. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
3. Clarify the water fixture unit calculations - waterless urinals normally do not require a water supply.
4. Provide the basis for the water distribution calculations (e.g. available water pressure, static lift, minimum residual water pressure, developed pipe length, etc). Revise the water pipe sizing shown on sheet P1.1 to correspond to the pipe sizing chart. Reference: Sections 604.1 and 604.3, IPC 2012.
05/06/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/07/2014 MARTIN BROWN FIRE REVIEW Approved
06/09/2014 KROBLES1 WWM REVIEW Needs Review