Permit Number: T14CM02601
Parcel: 110110670

Address:
4809 E TOWNER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM02601
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 6-04-14
Activity: T14CM02601
Address: 4809 E Towner St.
Applicant: Bill Rupert

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Correct references to the 2006 Outdoor Lighting Code to reflect the currently adopted 2012 edition.
2. Clarify why there are two ceiling areas specified on the ResCheck U-value alternative calculation.
3. The existing roof framing over the carport ceiling is not structurally approved to support the proposed ceiling, R801.2.
4. Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3901.2.
5. Provide circuit references for the proposed bathroom outlets, E3703.4, E3901.6.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/05/2014 CPIERCE1 REJECT SHELF Completed